Steel Cementitious Rigid Grid System
Specifications » Steel Cementitious Rigid Grid System

Recommended Applications

|
SYSTEM NAME Steel Cementitious Rigid Grid System
SYSTEM CODE SC- RG
COMPLIANT STANDARDS Australian Standard AS4154 / AS4155 Australian Standard AS1170 CISCA Standard UFGS - 09 69 11/15 PSA MOB PF2 1992 NATA Testing Certification IS09239 - 1 -2003 EN12825 - 2001 DIN4102- 1 -1998
|
DESCRIPTION The Steel Cementitious Rigid Grid System has been designed for pre finished flooring or office areas that require a more rigid installation. |
Specifiers Guide

The adjacent table details how to nominate the ASP Rigid Grid System in your project specification.
Access Floor Panel
|
|
Type: SC Series - Steel Cementitious Size: The panels are 600mm x 600mm in size and are interchangeable with other panels. Also available are a series of load bearing finishing panels designed to minimise small off cuts experienced when cutting around columns, curved building designs and finishing off near perimeter walls. These finishing panels come in 600 x 800mm and 600 x 300mm sizes. Depth: 33mm Construction: The panels consist of a hardened steel top and bottom sheet plate with corrosion resistant protection, inside and out, encapsulating a structural cementitious core. Core: Cementitious Compound Tolerance: ±0.25mm and a flatness tolerance of ±0.5mm measured on a diagonal across the top of the panel Finish: ASP's standard powder coated finish. Connection: The panel is screw fixed to the pedestal head at all four corners
|
Panel Load Tolerances
AUSTRALIAN STANDARD (AS)

Safety Factor: Panels must provide a minimum safety factor of 3 times the concentrated load specified above in accordance with AS4154-1993.
CISCA STANDARD
Safety Factor: Panels must provide a minimum safety factor of 5 times the uniform load specified above in accordance with ICC-ES AC300.
PSA MOB STANDARD

Safety Factor: Panels must provide a minimum safety factor of 3 times the concentrated load specified above in accordance with PSA MOB PF2 1992.
Access Floor Pedestals
|
|
Size: 10,000mm² base plate
Locking: The pedestals will be provided with an adjusting and locking nut to maintain the assembly at a selected height, which requires a deliberate action to change the height setting, and which prevents vibration displacement.
Finish: ASP’s standard powder coated finish.
Connection: The panel and stringer are screw fixed to the pedestal head at all four corners
Finished Floor Height (FFH): The finished floor height of the access floor is measured from the sub-floor to the top surface of the installed access floor.
|
Access Floor Stringers
![]() |
Type: SG6
Size: 600mm
Construction: The steel stringers shall be 31mm x 21mm x 1.2mm rectangular welded tube. The stringers shall be provided with a 3mm sponge rubber foam to provide sound absorbing buffer between the stringer and the panel.
Finish: Galvanized steel.
Connection: The bridging stringer is screw fixed to the pedestal head so that the entire system is engaged as a structural membrane.
|
-
Specifications: