Steel Cementitious Rigid Grid System

sc rigid grid

 

Recommended Applications

sc rigid grid recommend application

 

SYSTEM NAME

Steel Cementitious Rigid Grid System

 

SYSTEM CODE    

SC- RG

 

COMPLIANT STANDARDS  

Australian Standard AS4154 / AS4155   

Australian Standard AS1170   

CISCA Standard UFGS - 09 69 11/15

PSA MOB PF2 1992

NATA Testing Certification

IS09239 - 1 -2003

EN12825 - 2001

DIN4102- 1 -1998

 

DESCRIPTION 

The Steel Cementitious Rigid Grid System has been

designed for pre finished flooring or office areas that

require a more rigid installation. 

 

Specifiers Guide

sc rigid grid spec guide

The adjacent table details how to nominate the ASP Rigid Grid System in your project specification.

 

Access Floor Panel

 

sc rigid grid access floor panel

 

Type: SC Series - Steel Cementitious

Size: The panels are 600mm x 600mm in size and are interchangeable with other panels.

Also available are a series of load bearing finishing panels designed to minimise small off cuts experienced when cutting around columns, curved building designs and finishing off near perimeter walls. These finishing panels come in 600 x 800mm and 600 x 300mm sizes.

Depth: 33mm

Construction: The panels consist of a hardened steel top and bottom sheet plate with corrosion resistant protection, inside and out, encapsulating a structural cementitious core. 

Core: Cementitious Compound

Tolerance: ±0.25mm and a flatness tolerance of ±0.5mm measured on a diagonal across the top of the panel

Finish: ASP's standard powder coated finish.

Connection: The panel is screw fixed to the pedestal head at all four corners

 

 

Panel Load Tolerances  

AUSTRALIAN STANDARD (AS)

sc rigid grid aus standard

 Safety Factor: Panels must provide a minimum safety factor of 3 times the concentrated load specified above in accordance with AS4154-1993.

 

CISCA STANDARD

sc rigid grid cisca standard Safety Factor: Panels must provide a minimum safety factor of 5 times the uniform load specified above in accordance with ICC-ES AC300.

 

PSA MOB STANDARD

sc rigid grid PSA MOB standard

Safety Factor: Panels must provide a minimum safety factor of 3 times the concentrated load specified above in accordance with PSA MOB PF2 1992. 

 

Access Floor Pedestals

 

sc rigid grid access floor depestal

sc rigid grid access floor depestal 2

 

Size: 10,000mm² base plate  


Construction: Steel pedestal base and nickel chrome plated head assembly with a zinc electro‐plated rod

 

Locking: The pedestals will be provided with an adjusting and locking nut to maintain the assembly at a selected height, which requires a deliberate action to change the height setting, and which prevents vibration displacement.    

 

Finish: ASP’s standard powder coated finish. 

 

Connection: The panel and stringer are screw fixed to the pedestal head at all four corners

 

Finished Floor Height (FFH): The finished floor height of the access floor is measured from the sub-floor to the top surface of the installed access floor.

 

 

Access Floor Stringers

 sc rigid grid access floor stringer

 

Type: SG6

 

Size: 600mm

 

Construction: The steel stringers shall be 31mm x 21mm x 1.2mm rectangular welded tube. The stringers shall be provided with a 3mm sponge rubber foam to provide sound absorbing buffer between the stringer and the panel.

 

Finish: Galvanized steel.

 

Connection: The bridging stringer is screw fixed to the pedestal head so that the entire system is engaged as a structural membrane.